*Products' brief
*Electronic residual current device/ miniature circuit breaker combination in only 1MU
*Tripping line voltage dependent
*Contact position indicator red-green
*Permanently connected neutral conductor (950 mm long)
*Can be connected to standard busbar (at the lower side)
*Rated current:1/2/3/4/6/8/10/13/16/20/25/32/40A
| Electrical |
| Design according to IEC/EN 61009 |
| Current test marks as printed onto the device |
| Number of poles 1+N-pole |
| Pole switched, |
| N led through (solid neutral) |
| Rated voltage Un 240 VAC |
| Rated frequency 50/60 Hz |
| Rated current In 1-40 A |
| Rated tripping current IΔn 10,30,100,300 mA |
| Sensitivity AC |
| Endurance |
| Electro-mechanical comp. ≥4,000 operating cycles |
| Mechanical |
| Frame size 45 mm |
| Device height 120.5 mm |
| Device width 18 mm (1MU) |
| Mounting quick fastening with |
| 2 lock-in positions on |
| DIN rail IEC/EN 60715 |
| Upper terminals lift terminals |
| Lower terminals open mouthed/lift terminals |
| Terminal protection finger and hand touch safe, |
| Terminal capacity 1-25 mm 2 |
| Busbar thickness below 0.8-2 mm |
| Degree of protection,built-in IP40 |
| Perm.ambient temperature range -5°C to + 40°C |
| Resistance to climatic conditions acc.to IEC60068-2 |
| Tripping Characteristic RCD component: |
| Tripping |
| line voltage-dependent instantaneous |
| Peak withstand current 250A (8/20U) |
| Rated non-tripping current IΔno 0.5 IΔn |
| Voltage range for protective function 184-264 V~ |
| Tripping Characteristic MCB component: |
| Conventional non-tripping current 1.13 In |
| Conventional tripping current 1.45 In |
| Reference temperature 30°C |
| Selectivity class 3 |
| Maximum back-up fuse > 6 kA 100 A gL |
| Ultimate short circuit breaking capacity Imn |
| Type B 3 In <Imt ≤5 In:t(Imt)<0,1s |
| Type C 5 In <Imt ≤10 In:t(Imt)<0,1s |
| Type D 10 In <Imt ≤20 In:t(Imt)<0,1s |
| Ultimate short circuit breaking capacity Icn 6 kA |
| Rated short circuit breaking capacity Inc 6 kA |
| Rated fault breaking capacity IΔm 6 kA |