Home » Product List » Protective breaker » RCBO (RLC02-M)
Product Details
RCBO (RLC02-M)
| Model NO.: | RLC02-M |
|---|
Product Description
Products' brief:
*Combined RCD/MCB device
*Line voltage-independent tripping
*Compatible with standard busbar
*Twin-purpose terminal (lift/open-mouthed) above and below
*Busbar positioning optionally above or below
*Free terminal space despite installed busbar
*Guide for secure terminal connection
*Contact position indicator red-green
*Type-A: Protects against special forms of residual pulsating DC which have not been smoothed
*Rated current:1/2/3/4/6/10/13/16/20/25/32/40
| Electrical |
| Design according to IEC/EN 61009 |
| Current test marks as printed onto the device |
| Tripping |
| line voltage-independent instantaneous 250A(8/20U) |
| surge current-proof; |
| Rated voltage Ue 230 V; 50 Hz |
| Operational voltage range 196-253 V |
| Rated tripping current IΔN 10,30,100,300 mA |
| Rated non-tripping current IΔNo 0.5 IΔN |
| Sensitivity AC and pulsating DC |
| Selectivity class 3 |
| Rated breaking capacity 4.5 kA |
| Rated current 2-40 A |
| Rated peak withstand voltage Uimp 6 kV(1.2/50U) |
| Characteristic B/C/D |
| Maximum back-up fuse (short circuit) 100 A gL(>4,5kA) |
| Endurance |
| electro-mechanical comp ≥4,000 operating cycles |
| Mechanical |
| Frame size 45 mm |
| Device height 86.4 mm |
| Device width 36 mm (2MU) |
| Mounting 3-position DIN rail clip, |
| permits removal from |
| existing busbar system |
| Upper and lower terminals open mouthed/lift terminals |
| Terminal protection finger and hand touch safe, |
| Terminal capacity 1-25 mm2 |
| Busbar thickness 0.8-2 mm |
| Degree of protection switch IP20 |
| Degree of protection,built-in IP40 |
| Tripping temperature -5°C to + 40°C |
| Resistance to climatic conditions acc.to IEC/EN 61009 |
Inquiry Basket (